Amps to kW

Turn a clamp-meter current reading into the real power a circuit is actually consuming.

Amps to kW Calculator

kW = √3 × V × A × PF ÷ 1,000
100 A
A
400 V
V
Quick values
0.85 PF
PF
Quick values

At a glance

kW = √3 × V × A × PF ÷ 1,000
Real power
58.89 kW
Measured current
100 A
Voltage
400 V
Power factor
0.85 PF
Supply type
3

Every diagram and table on this page updates with the calculator above.

Output

Live
Real power
58.89kW
kW = (√3 × 400 V × 100 A × 0.85) ÷ 1,000 = 58.89 kW
Apparent power69.28 kVA
Reactive power36.5 kVAR
Real power58,889.7 W

The Amps to kW Formula

kW (3-phase) = √3 × V × A × PF ÷ 1,000
kW (1-phase) = V × A × PF ÷ 1,000

Same expression with the √3 removed.

Without a power factor you can only reach kVA. Current and voltage alone tell you what the supply is carrying, never how much of it is doing work.

The conversion

Live
Input100A
Result58.89kW
Measured current to real power

Why a Clamp Meter Alone Is Not Enough

A clamp meter reads current magnitude, not its phase relationship to voltage. Two circuits with identical current can consume very different amounts of power.

Move the power factor slider: the current wave slides out of step with voltage while its height stays exactly the same. That shift is invisible to a basic clamp meter.

True RMS matters too

On circuits with drives, rectifiers or LED drivers, an averaging meter can read 10–40% low. Use a true-RMS instrument on anything non-linear.

Voltage and current

Live
Voltage CurrentShift 31.8°
Voltage (copper) and current (teal)

Measuring a Circuit Properly

  1. Clamp one conductor only

    Enclosing two conductors gives the vector sum, which on a balanced pair is close to zero.

  2. Measure all three phases

    Unbalance is common. Use the highest reading for cable checks and the average for an energy estimate.

  3. Record the voltage at the same moment

    Supply voltage moves through the day; pairing a morning current with an evening voltage introduces error.

  4. Get the power factor

    Use a power analyser if you can. Otherwise take it from the motor nameplate at the observed loading.

  5. Note the load condition

    A reading taken during a lull is not the design figure. Capture the peak you actually need to size for.

Sanity check against the nameplate

If your calculated kW exceeds the equipment rating, one of the inputs is wrong — usually the power factor or a clamp around the wrong conductor.

Same amps, three answers

Live
PF 0.70
Real power
48.5 kW
Reactive
49.48 kVAR
PF 0.85
Real power
58.89 kW
Reactive
36.5 kVAR
PF 0.95
Real power
65.82 kW
Reactive
21.63 kVAR
The same current reading interpreted three ways

Amps to kW Conversion Chart

Standard breaker-sized current readings converted at your voltage, power factor and supply type.

Conversion chart

Live
AReal power (kW)Apparent power (kVA)
5 A2.943.46
10 A5.896.93
16 A9.4211.09
20 A11.7813.86
25 A14.7217.32
32 A18.8422.17
40 A23.5627.71
63 A37.143.65
80 A47.1155.43
100 A58.8969.28
125 A73.6186.6
160 A94.22110.85
200 A117.78138.56
250 A147.22173.21
400 A235.56277.13
630 A371.01436.48

Power for Every Current and Voltage

Useful when you know the breaker size but not the supply arrangement — read across to compare voltages at a glance.

kW lookup grid

Live
kW for each A × V combination
A230 V400 V415 V480 V
16 A5.49.49.811.3
32 A10.818.819.622.6
63 A21.337.138.544.5
100 A33.958.961.170.7
160 A54.294.297.8113.1
250 A84.7147.2152.7176.7
400 A135.4235.6244.4282.7

From Meter Reading to Billed Demand

Utilities bill energy in kilowatt-hours and often charge separately for peak demand and for poor power factor. All three numbers come from the same measurement.

QuantityFrom this calculationWhere it appears
Real powerkWEnergy charge, once multiplied by hours
Apparent powerkVAMaximum demand charge on many tariffs
Reactive powerkVARPower factor penalty or kVArh charge

The gap between the two bars is capacity your supply carries without earning anything — the exact quantity that power factor correction removes.

Breakdown of the load

Live
69.3kVA drawn
  • Real power58.9 kW
  • Reactive power36.5 kVAR
What your measured current is actually made of

Amps to kW Questions

Common questions about converting amps to kw.

Three phase: kW = √3 × V × A × PF ÷ 1,000. Single phase: kW = V × A × PF ÷ 1,000.

About 58.9 kW at 0.85 power factor, or 55.4 kW at 0.80.

Not accurately. You can get kVA from volts and amps, but real power needs the power factor.

Use 0.85 for a general industrial circuit, 0.80 for motor-dominated loads, and 0.95 or better for corrected installations or modern electronics.

It can if the load is unbalanced. Measure each phase and use the highest reading for cable sizing, or the average for an energy estimate.

You have probably clamped more than one conductor. The meter sums the currents, and on a balanced pair they cancel.

On anything with drives, rectifiers or electronic ballasts, yes. Averaging meters can under-read distorted current by 10–40%.