VA to kW

Convert a volt-ampere rating into the kilowatts of real power it delivers at your load power factor.

VA to kW Calculator

kW = VA × PF ÷ 1,000
1,500 VA
VA
0.9 PF
PF
Quick values

At a glance

kW = VA × PF ÷ 1,000
Real power
1.35 kW
Apparent power
1,500 VA
Power factor
0.9 PF

Every diagram and table on this page updates with the calculator above.

Output

Live
Real power
1.35kW
kW = 1,500 VA × 0.9 PF ÷ 1,000 = 1.35 kW
In watts1,350 W
Apparent power1.5 kVA

The VA to kW Formula

kW = VA × PF ÷ 1,000

Without the power factor you only know the current the supply must carry, not the work done.

A 1,500 VA supply at 0.9 power factor delivers 1.35 kW. The missing 150 VA is not lost as heat — it flows back and forth between source and load every cycle, doing nothing but occupying the cable.

The conversion

Live
Input1,500VA
Result1.35kW
Apparent power to real power

What the Power Factor Is Doing

Power factor is the cosine of the angle between the voltage and current waves. When current lags voltage, part of every cycle pushes energy back towards the source instead of into the load.

  • At unity power factor the two waves peak together and every joule goes into the load.
  • At 0.9 the current lags by about 26°, and 10% of the apparent power does nothing.
  • At 0.5 the current lags by 60°, and half the supplied capacity is wasted.
Harmonics distort the picture

Switch-mode supplies without correction draw current in sharp spikes rather than a lagging sine wave. The result is a poor true power factor even though the displacement angle looks fine.

Voltage and current

Live
Voltage CurrentShift 25.8°
Voltage (copper) and current (teal) over one cycle

Inside a Switch-Mode Power Supply

The reason a modern power supply has a power factor at all is its input stage. A bare rectifier and capacitor draws current only at the peaks of the voltage wave, producing a spiky, harmonic-rich current.

  1. Rectify

    The incoming AC is converted to DC, charging a bulk capacitor near the peak of each half-cycle.

  2. Correct (if fitted)

    Active PFC shapes the input current back into a sine wave in phase with voltage, lifting true power factor above 0.95.

  3. Switch and regulate

    A high-frequency converter produces the output rails your equipment actually uses.

This is why two 500 W devices can present very different loads to a UPS: the one with active PFC draws around 520 VA, while an uncorrected unit can demand 800 VA or more.

Useful share

Live
1.4kW useful
  • Real power1.4 kW
  • Apparent power1.5 kVA
Useful power as a share of what the supply must carry

VA to kW Conversion Chart

Everyday VA ratings converted at your selected power factor.

Conversion chart

Live
VAReal power (kW)Real power (W)
100 VA0.0990
250 VA0.225225
500 VA0.45450
650 VA0.585585
750 VA0.675675
1,000 VA0.9900
1,500 VA1.351,350
2,000 VA1.81,800
3,000 VA2.72,700
5,000 VA4.54,500
7,500 VA6.756,750
10,000 VA99,000
15,000 VA13.513,500
20,000 VA1818,000

Reading the Label on an Adapter

MarkingWhat it meansUse it for
Input: 100–240 V ~ 1.5 AWorst-case input current at the lowest voltageCircuit and fuse sizing
Input: 150 VAApparent power drawn from the supplyUPS and cable capacity
Output: 19 V ⎓ 4.7 ADC output, about 89 WWhat the device actually receives
Efficiency: 88%Output ÷ input real powerEstimating heat and running cost

A 90 W laptop adapter

Given
  • Output: 19 V × 4.74 A = 90 W
  • Efficiency: 88%
  • Input power factor: 0.95
Working
  1. Input real power = 90 ÷ 0.88 = 102 W
  2. Input VA = 102 ÷ 0.95 = 108 VA

The adapter draws about 108 VA and delivers 90 W, wasting roughly 12 W as heat.

Three PSU designs

Live
No PFC (0.65)
Real power
975 W
Apparent
1.5 kVA
Passive PFC (0.8)
Real power
1,200 W
Apparent
1.5 kVA
Active PFC (0.99)
Real power
1,485 W
Apparent
1.5 kVA
The same VA rating across three power supply designs

Auditing a Small Office

Converting VA to kW is usually a step in a bigger job: working out what a floor actually draws so you can size a supply, a UPS or a standby generator without guessing.

  1. List every device

    Record the input VA or the input voltage and current from each nameplate.

  2. Measure a sample

    Plug-in meters cost little and typically reveal 30–50% less real consumption than nameplates claim.

  3. Apply diversity

    Nothing runs flat out simultaneously. A diversity factor of 0.6–0.8 is realistic for office equipment.

  4. Convert and total

    Turn each VA figure into kW at its own power factor, then add the kilowatts.

30–50%Typical nameplate overstatement
0.6–0.8Realistic diversity factor
0.9+Power factor of modern IT gear

Watts vs VA

Live
18,0000020,000Apparent power (VA)
1,500 VA1,350 W
Real power across the full VA range at your power factor

VA to kW Questions

Common questions about converting va to kw.

Multiply the VA figure by the power factor and divide by 1,000: kW = VA × PF ÷ 1,000.

0.9 kW at 0.9 power factor, 0.8 kW at 0.8, and 1 kW at unity power factor.

Only at unity power factor. VA measures apparent power, watts measure real power; in AC circuits watts are usually the smaller number.

Use VA. Cables, breakers and UPS inverters are limited by current, which follows apparent power rather than watts.

Assume 0.8 for mixed or motor loads and 0.9–0.95 for modern electronic equipment, then confirm against the nameplate or a measurement before final design.

Because their input power factors differ. A device with active PFC draws around 520 VA for 500 W; an uncorrected one can demand 800 VA for the same output.

Usually, yes — often by 30–50%. Nameplates state worst-case draw at the lowest supply voltage, which real operation rarely approaches.