kVA to Amps

Work out the line current an apparent-power rating draws, on either a single-phase or three-phase supply.

kVA to Amps Calculator

A = kVA × 1,000 ÷ (V × √3 for 3-phase)
100 kVA
kVA
400 V
V
Quick values

At a glance

A = kVA × 1,000 ÷ (V × √3 for 3-phase)
Line current
144.3 A
Apparent power
100 kVA
Line voltage
400 V
Supply type
3

Every diagram and table on this page updates with the calculator above.

Output

Live
Line current
144.3A
A = (100 × 1,000) ÷ (√3 × 400 V) = 144.3 A
Apparent power100 kVA

The kVA to Amps Formula

Two formulas, one difference: three-phase divides by an extra √3.

A (1-phase) = kVA × 1,000 ÷ V
A (3-phase) = kVA × 1,000 ÷ (√3 × V)

√3 ≈ 1.732, and V is the line-to-line voltage.

Power factor never appears here

Current follows apparent power. That is precisely why cables and breakers are sized from kVA and not from kW.

The conversion

Live
Input100kVA
Result144.34A
Apparent power to line current

Why √3 Appears in Three Phase

Three-phase supplies carry three voltage waves spaced 120° apart. Because the peaks do not coincide, the line-to-line voltage is √3 times the line-to-neutral voltage, and the system delivers √3 times more power for the same line current.

Line voltage (V_LL)
Between any two phases — 400 V on a typical European board.
Phase voltage (V_LN)
Between a phase and neutral — 230 V on the same board, because 400 ÷ √3 = 230.
Line current
The current in each conductor; the quantity this calculator returns.

The practical consequence is that a three-phase feeder needs only 58% of the current a single-phase one would for the same kVA — which is why industry runs on three phases.

Three-phase waveforms

L1 L2 (120°) L3 (240°)
Three voltages, 120° apart

Current Sets the Cable and Breaker

  1. Find full-load current

    Use the formula above with the actual supply voltage and phase configuration.

  2. Apply derating

    Grouped cables, high ambient temperature, thermal insulation and buried runs all reduce capacity — sometimes by half.

  3. Pick a conductor

    Choose a cross-section whose derated capacity exceeds the design current.

  4. Check volt drop

    On long runs the drop limit, not the current limit, usually decides the size.

  5. Verify disconnection

    Confirm earth fault loop impedance allows the protective device to operate in time.

Design currentTypical breakerIndicative copper CSA
Up to 16 A16 A1.5 – 2.5 mm²
16 – 25 A25 A4 mm²
25 – 40 A40 A6 – 10 mm²
40 – 63 A63 A16 mm²
63 – 100 A100 A25 – 35 mm²
100 – 160 A160 A50 – 70 mm²

Indicative only — always size from the installation method and the applicable wiring standard.

Current gauge

Live
01,000
144.34 ALine current
Your result across a typical LV distribution range

kVA to Amps Chart

Standard ratings at your selected voltage and supply type. Switch between single and three phase to watch the current fall.

Conversion chart

Live
kVALine current (A)
5 kVA7.2
10 kVA14.4
15 kVA21.7
20 kVA28.9
25 kVA36.1
30 kVA43.3
50 kVA72.2
75 kVA108.3
100 kVA144.3
150 kVA216.5
200 kVA288.7
300 kVA433
500 kVA721.7
750 kVA1,082.5
1,000 kVA1,443.4

Current at Every Rating and Voltage

The grid recalculates for whichever supply type is selected in the calculator, so the same table answers both the single-phase and three-phase question.

Current lookup grid

Live
A for each kVA × V combination
kVA208 V230 V400 V415 V480 V
10 kVA2825141412
25 kVA6963363530
50 kVA139126727060
100 kVA278251144139120
200 kVA555502289278241
500 kVA1,3881,255722696601
1,000 kVA2,7762,5101,4431,3911,203

Current Rises Proportionally with kVA

At fixed voltage, current is a straight line through the origin. Doubling the connected apparent power doubles the current, and with it the heating in every conductor along the route.

Losses rise with the square

Conductor loss is I²R. Doubling the current quadruples the heat — which is why upgrading a feeder often costs far more than the extra load appears to justify.

Current against kVA

Live
2,886.8002,000Apparent power (kVA)
100 kVA144.34 A
Line current across the full rating range at your voltage

Four Ways to Get the Current Wrong

Wrong voltage type

Using phase-to-neutral voltage with the √3 formula understates the current by a factor of three.

Applying power factor

Power factor belongs in the kW calculation, not the current one. Including it here undersizes the cable.

Forgetting derating

A cable in a grouped, hot, insulated run can lose 40% or more of its tabulated capacity.

Sizing at exactly full load

Select the next standard device above the design current, never the one below it.

Voltage comparison

Live
230 V
Current
251 A
400 V
Current
144.3 A
690 V
Current
83.7 A
The same apparent power at three distribution voltages

kVA to Amps Questions

Common questions about converting kva to amps.

For single phase, A = kVA × 1,000 ÷ V. For three phase, divide by √3 × V as well.

About 144 A: 100 × 1,000 ÷ (1.732 × 400). At 230 V single phase the same rating would draw roughly 435 A.

No. Current follows apparent power, so the kVA figure alone determines it. Power factor only matters when converting to kW.

The three phases share the load and their voltages are 120° apart, giving a √3 advantage. The same kVA needs about 58% of the single-phase current.

No. Select the next standard rating above the full-load current, and apply derating factors for ambient temperature, grouping and installation method.

Line-to-line voltage. Using the phase-to-neutral figure with the √3 formula gives a result three times too small.

It falls in inverse proportion. Doubling the distribution voltage halves the current for the same kVA, which is why large sites distribute at 690 V or higher.