kVA to Amps — Three Phase

Full-load current for three-phase transformers, generators and switchboards, with the real power they deliver.

kVA to Amps (Three Phase) Calculator

A = kVA × 1,000 ÷ (√3 × V)
500 kVA
kVA
400 V
V
Quick values
0.8 PF
PF
Quick values

At a glance

A = kVA × 1,000 ÷ (√3 × V)
Full-load current
721.7 A
Apparent power
500 kVA
Line-to-line voltage
400 V
Power factor
0.8 PF

Every diagram and table on this page updates with the calculator above.

Output

Live
Full-load current
721.7A
A = (500 × 1,000) ÷ (√3 × 400 V) = 721.7 A
Real power400 kW

Three-Phase Current Formula

A = kVA × 1,000 ÷ (√3 × V)

V is the line-to-line voltage. √3 ≈ 1.7320508.

A 500 kVA transformer at 400 V

Given
  • Rating: 500 kVA
  • Secondary voltage: 400 V line-to-line
Working
  1. A = 500 × 1,000 ÷ (1.732 × 400)
  2. A = 500,000 ÷ 692.8

About 722 A per phase on the low-voltage side.

The conversion

Live
Input500kVA
Result721.69A
Three-phase full-load current

Star, Delta and the Line/Phase Trap

Most three-phase errors come from mixing line and phase quantities. The relationship flips depending on whether the windings are connected in star or delta.

ConnectionVoltageCurrent
Star (wye)V_line = √3 × V_phaseI_line = I_phase
DeltaV_line = V_phaseI_line = √3 × I_phase

The √3 appears exactly once in each configuration — on voltage for star, on current for delta.

The formula on this page always returns line current from line voltage, which is what you need for cables, breakers and switchboards. Phase current only matters inside the machine.

Phase relationship

L1 L2 (120°) L3 (240°)
Three phase voltages, 120° apart

Full-Load Current for Standard Transformers

Common three-phase ratings at your selected voltage, with the kilowatts each supports at your power factor.

Transformer chart

Live
kVAFull-load current (A)Real power (kW)
25 kVA36.120
50 kVA72.240
75 kVA108.360
100 kVA144.380
150 kVA216.5120
200 kVA288.7160
250 kVA360.8200
315 kVA454.7252
400 kVA577.4320
500 kVA721.7400
630 kVA909.3504
800 kVA1,154.7640
1,000 kVA1,443.4800
1,250 kVA1,804.21,000
1,600 kVA2,309.41,280
2,000 kVA2,886.81,600

Higher Voltage, Lower Current

Current is inversely proportional to voltage. That single fact drives the whole architecture of industrial distribution: move power at the highest practical voltage, step down close to the load.

÷2Current when voltage doubles
÷4Losses when voltage doubles
690 VCommon large-plant LV level

Drag the voltage slider and watch the curve fall away. The kVA has not changed — only the current needed to move it.

Current against voltage

Live
1,519.30190690Line voltage (V)
400 V721.69 A
Full-load current across the whole voltage range at your rating

Full-Load Current Lookup Grid

Every standard rating against every common distribution voltage, recalculated live.

Current lookup grid

Live
A for each kVA × V combination
kVA208 V400 V415 V480 V690 V
100 kVA27814413912084
250 kVA694361348301209
500 kVA1,388722696601418
800 kVA2,2211,1551,113962669
1,000 kVA2,7761,4431,3911,203837
1,600 kVA4,4412,3092,2261,9251,339
2,000 kVA5,5512,8872,7822,4061,673

From Full-Load Current to Switchgear

Full-load current sets the continuous rating, but protective devices also have to handle fault current, and that is set by the transformer impedance rather than its kVA.

  1. Continuous rating

    Choose a device rated above the full-load current after any derating for enclosure temperature.

  2. Fault level

    Approximate prospective fault current as full-load current ÷ per-unit impedance. A 500 kVA unit at 5% gives roughly 20 × FLC.

  3. Breaking capacity

    The device must interrupt that fault current safely — check the kA rating, not just the amp rating.

  4. Discrimination

    Confirm the upstream device does not trip before the downstream one on a downstream fault.

Switchboard checklist
  • Incomer rated above transformer full-load current.
  • Breaking capacity exceeds prospective fault current.
  • Busbar rated for both continuous current and fault withstand.
  • Protection settings discriminate with upstream and downstream devices.
  • Ambient temperature derating applied inside the enclosure.

Current gauge

Live
03,000
721.69 AFull-load current

kVA to Amps (Three Phase) Questions

Common questions about converting kva to amps (three phase).

A = kVA × 1,000 ÷ (√3 × V), using the line-to-line voltage. √3 is approximately 1.732.

About 722 A per phase on the low-voltage side.

Use line-to-line voltage with the √3 formula. Line-to-neutral would need a different expression and is a common source of errors.

No. Select the next standard breaker above the full-load current, after applying derating for temperature, grouping and installation method.

Current is fixed by apparent power. Power factor only tells you how much of that current becomes useful kilowatts.

Divide full-load current by the per-unit impedance. A 500 kVA transformer at 5% impedance gives roughly twenty times its full-load current.

No, as long as you use line voltage and line current. The configuration only matters when you need the current inside the windings.