kVA to kW — Single Phase

Convert a single-phase kVA rating to kilowatts and see the line current it draws at your supply voltage.

kVA to kW (Single Phase) Calculator

kW = kVA × PF
10 kVA
kVA
0.85 PF
PF
Quick values
230 V
V
Quick values

At a glance

kW = kVA × PF
Real power
8.5 kW
Apparent power
10 kVA
Power factor
0.85 PF
Supply voltage
230 V

Every diagram and table on this page updates with the calculator above.

Output

Live
Real power
8.5kW
kW = 10 kVA × 0.85 PF = 8.5 kW
Line current43.5 A
Reactive power5.27 kVAR

Single-Phase kVA to kW Formula

kW = kVA × PF

Identical in single and three-phase systems — only the current calculation differs.

The conversion itself carries no phase information at all. What changes between single and three-phase is how much current that apparent power represents, because the three-phase formula includes a √3 factor.

A = kVA × 1,000 ÷ V

Single-phase current: no √3 anywhere.

The conversion

Live
Input10kVA
Result8.5kW
Single-phase conversion

Single Phase vs Three Phase

Single phaseThree phase
kVA → kWkVA × PFkVA × PF
CurrentkVA × 1,000 ÷ VkVA × 1,000 ÷ (√3 × V)
Typical voltage120 / 230 / 240 V208 / 400 / 415 / 480 V
Practical ceiling~20 kVAHundreds of kVA
Motor startingNeeds a start capacitorSelf-starting

Above roughly 15–20 kVA the single-phase current becomes awkward: 20 kVA at 230 V is 87 A, which needs heavy cable and a substantial service fuse. Three phase moves the same power at 58% of the current.

Voltage comparison

Live
120 V
Current
83.3 A
Real power
8.5 kW
230 V
Current
43.5 A
Real power
8.5 kW
240 V
Current
41.7 A
Real power
8.5 kW
The same kVA at three common single-phase voltages

Real and Reactive Split

On a single-phase supply the reactive component still consumes cable and transformer capacity even though it performs no work. Domestic and light commercial loads are often worse than industrial ones because of lightly loaded motors in fridges, pumps and fans.

Why this matters on a small supply

A 100 A single-phase service at 230 V is a 23 kVA supply. At 0.85 power factor that is only 19.6 kW of usable load — the difference is a whole electric shower.

Power triangle

Live
8.5 kW5.27 kVAR10 kVA
kVA is the hypotenuse

Choosing the Breaker and Cable

Protect the circuit for the current the kVA draws, not the kW. A 10 kVA single-phase supply at 230 V pulls about 43 A regardless of how good the power factor is.

  1. Calculate full-load current

    A = kVA × 1,000 ÷ V. Use the actual nominal supply voltage, not a rounded figure.

  2. Apply derating factors

    Grouping, ambient temperature and insulation type all reduce a cable current-carrying capacity.

  3. Select the next standard device

    Choose the next rating above the derated current — 16, 20, 25, 32, 40, 50, 63 A and so on.

  4. Check volt drop

    Long runs often need a larger cable than the current alone suggests. Most standards limit drop to 3–5%.

  • Full-load current calculated from kVA, not kW.
  • Derating applied for grouping and ambient temperature.
  • Volt drop within the limit for the circuit length.
  • Protective device coordinates with the upstream supply fuse.
  • Earth fault loop impedance verified for disconnection time.

Current gauge

Live
0200
43.48 ALine current
Your current against a common domestic and light-commercial range

Single-Phase Conversion Chart

Typical single-phase ratings with real power and line current at your selected voltage and power factor.

Conversion chart

Live
kVAReal power (kW)Line current (A)
1 kVA0.854.3
2 kVA1.78.7
3 kVA2.5513
5 kVA4.2521.7
7.5 kVA6.3832.6
10 kVA8.543.5
15 kVA12.7565.2
20 kVA1787
25 kVA21.25108.7
30 kVA25.5130.4
40 kVA34173.9
50 kVA42.5217.4
75 kVA63.75326.1
100 kVA85434.8

Current for Every Rating and Voltage

Because current depends only on kVA and voltage, this grid stays valid whatever the power factor. It is the fastest way to check whether a proposed single-phase supply is realistic.

Current lookup grid

Live
A for each kVA × V combination
kVA110 V120 V220 V230 V240 V
2 kVA18.216.79.18.78.3
5 kVA45.541.722.721.720.8
10 kVA90.983.345.543.541.7
15 kVA136.412568.265.262.5
20 kVA181.8166.790.98783.3
30 kVA272.7250136.4130.4125
50 kVA454.5416.7227.3217.4208.3

What a Typical Domestic Supply Gives You

60 A service

About 13.8 kVA at 230 V — older housing stock, tight for electric heating.

100 A service

About 23 kVA, the common modern domestic supply in much of Europe.

80 A US service

Two 120 V legs giving 240 V; a 200 A panel is roughly 48 kVA.

Before adding an electric vehicle charger, a heat pump or a shower, check the headroom against the service fuse rather than the consumer unit — the fuse is the real limit.

Supply split

Live
How the supply divides
62%
38%
  • Usable real power8.5 kW
  • Reactive component5.3 kVAR

kVA to kW (Single Phase) Questions

Common questions about converting kva to kw (single phase).

No. kW = kVA × PF applies to single and three-phase alike. Only the current formula changes, because three-phase includes √3.

8.5 kW at 0.85 power factor, 8 kW at 0.80, and 10 kW at unity power factor.

About 43.5 A, found from amps = kVA × 1,000 ÷ volts.

The service fuse and cable limit current. At a fixed voltage that current caps the apparent power, which is why supplies are quoted in kVA or amps.

Above roughly 15–20 kVA, three-phase reduces line current for the same power, allowing smaller conductors and supporting three-phase motors.

About 23 kVA at 230 V, which is 19.6 kW at 0.85 power factor. Diversity means the connected load can exceed this, but the peak must not.

Yes, in inverse proportion. The same 10 kVA draws 83 A at 120 V but only 43.5 A at 230 V.