kW to CFM

Find the airflow in cubic feet per minute needed to carry a heating or cooling load.

kW to CFM Calculator

CFM = BTU/hr ÷ (1.08 × ΔT)
10 kW
kW
20 °F
°F
Quick values

At a glance

CFM = BTU/hr ÷ (1.08 × ΔT)
Airflow
1,580 CFM
Thermal load
10 kW
Air temperature difference
20 °F

Every diagram and table on this page updates with the calculator above.

Output

Live
Airflow
1,580CFM
CFM = 34,121.4 BTU/hr ÷ (1.08 × 20 °F) = 1,580 CFM
In cubic metres per hour2,684 m³/h
Heat rate34,121 BTU/hr

The kW to CFM Formula

CFM = BTU/hr ÷ (1.08 × ΔT)

The 1.08 combines air density, specific heat and 60 minutes per hour at sea level.

  1. Convert the load to BTU/hr by multiplying kilowatts by 3,412.142.
  2. Decide the supply-to-room temperature difference you will design for.
  3. Divide by 1.08 × ΔT to get the airflow in cubic feet per minute.

Note: Standard air at sea level; correct for altitude and high temperatures.

The conversion

Live
Input10kW
Result1,579.7CFM
Thermal load to airflow

Air Carries Far Less Heat Than Water

PropertyAirWater
Density1.2 kg/m³1,000 kg/m³
Specific heat1.005 kJ/kg·K4.18 kJ/kg·K
Heat per m³ per K1.2 kJ4,180 kJ
Relative capacity1about 3,500

A cubic metre of water carries roughly 3,500 times the heat of a cubic metre of air for the same temperature change. That is why air systems need ducts measured in hundreds of millimetres while the equivalent pipework fits in your hand.

Heat transfer

Live
Load34,121 BTU/hr
Supply air
1,579.7 CFM
T = 20 °F
Return air
Load carried by the air stream

Airflow by Thermal Load

Required airflow across a range of loads at your design temperature difference.

Airflow chart

Live
kWAirflow (CFM)Airflow (m³/h)
1 kW158268
2.5 kW395671
5 kW7901,342
7.5 kW1,1852,013
10 kW1,5802,684
15 kW2,3704,026
20 kW3,1595,368
30 kW4,7398,052
50 kW7,89813,420
75 kW11,84820,129
100 kW15,79726,839
150 kW23,69540,259
250 kW39,49267,098

Airflow for Every Load and Delta-T

A wider supply temperature difference cuts the airflow needed — but too wide causes draughts and poor mixing, so comfort sets a practical floor on supply temperature.

Airflow lookup grid

Live
CFM for each kW × °F combination
kW10 °F15 °F20 °F25 °F40 °F
2 kW632421316253158
5 kW1,5801,053790632395
10 kW3,1592,1061,5801,264790
20 kW6,3194,2133,1592,5281,580
50 kW15,79710,5317,8986,3193,949
100 kW31,59421,06315,79712,6387,898
200 kW63,18842,12531,59425,27515,797

From Airflow to Duct Size

A common rule of thumb in comfort cooling is 400 CFM per ton of refrigeration, which corresponds to roughly a 20 °F supply temperature difference. Duct velocity then sets the cross-section.

LocationVelocity limitReason
Main plant risers1,500 – 2,500 fpmSpace efficiency, noise acceptable
Branch ducts800 – 1,200 fpmBalance between size and noise
Final runouts500 – 700 fpmNoise in occupied spaces
Return air grilles400 – 600 fpmAvoid whistling at the grille
  1. Size for thermal airflow

    Use the figure from this calculator as the starting point.

  2. Check ventilation requirements

    Fresh air rates per person may exceed the thermal airflow in densely occupied spaces.

  3. Check air changes per hour

    Some rooms have a minimum ACH requirement regardless of load.

  4. Take the highest of the three

    The governing figure is whichever is largest — never the average.

Airflow gauge

Live
05,000
1,579.7 CFMRequired airflow

Altitude and Temperature Change the Constant

The 1.08 constant assumes standard sea-level air. Thinner air carries less heat per cubic foot, so high-altitude installations need more airflow for the same duty.

AltitudeDensity ratioEffective constant
Sea level1.001.08
1,000 m (3,300 ft)0.910.98
1,500 m (5,000 ft)0.860.93
2,500 m (8,200 ft)0.780.84

A 20 kW load at 1,500 m

Given
  • Load: 20 kW = 68,243 BTU/hr
  • ΔT: 20 °F
  • Effective constant: 0.93
Working
  1. Sea level: 68,243 ÷ (1.08 × 20) = 3,159 CFM
  2. At altitude: 68,243 ÷ (0.93 × 20) = 3,669 CFM

About 16% more airflow — and a correspondingly larger fan and duct.

Airflow against delta-T

Live
31,593.90160Temperature difference (°F)
20 °F1,579.7 CFM
Required airflow across the whole delta-T range at your load

kW to CFM Questions

Common questions about converting kw to cfm.

Convert to BTU/hr, then divide by 1.08 × ΔT in °F. The airflow depends on the temperature difference you design for.

About 1,580 CFM at a 20 °F difference.

Air density (0.075 lb/ft³) × specific heat (0.24 BTU/lb·°F) × 60 minutes per hour, at standard sea-level conditions.

Around 400 CFM per ton is the common comfort-cooling rule of thumb, which corresponds to roughly a 20 °F supply temperature difference.

Yes. Thinner air carries less heat per cubic foot, so the constant falls and more airflow is needed at high elevation.

Take the larger figure. Fresh air requirements and minimum air change rates can govern in densely occupied spaces.