VA to kVA

Turn a volt-ampere rating from a UPS, small transformer or equipment label into kilovolt-amperes.

VA to kVA Calculator

kVA = VA ÷ 1,000
1,500 VA
VA
0.9 PF
PF
Quick values

At a glance

kVA = VA ÷ 1,000
Apparent power
1.5 kVA
Apparent power
1,500 VA
Power factor
0.9 PF

Every diagram and table on this page updates with the calculator above.

Output

Live
Apparent power
1.5kVA
kVA = 1,500 VA ÷ 1,000 = 1.5 kVA
Real power at this PF1.35 kW

The VA to kVA Formula

kVA = VA ÷ 1,000

The "k" prefix means a thousand, exactly as it does for grams or metres.

A 1,500 VA UPS is a 1.5 kVA UPS. Same machine, same capacity, different notation — manufacturers switch to kVA somewhere above 3,000 VA because the numbers get unwieldy.

The conversion

Live
Input1,500VA
Result1.5kVA
Unit change only

Which Equipment Is Labelled in VA

Desktop UPS

Almost always VA, typically 350–3,000 VA, usually with a separate watt figure alongside.

Control transformers

Machine control circuits are specified in VA because contactor coils are rated in VA too.

Isolation transformers

Medical and audio isolation units sit in the 100–5,000 VA range.

Lighting drivers

LED and fluorescent drivers list VA input alongside their watt output.

The pattern is consistent: anything small enough that kVA would be an awkward fraction gets labelled in volt-amperes instead.

Equipment scale

Live
100 VA
1 kVA
10 kVA
100 kVA
1,500 VA

The Two Limits on Every UPS

A UPS carries two ratings and your load has to respect both. The VA figure limits current through the inverter and the transfer switch; the watt figure limits the real power the battery and electronics can sustain.

VA rating
Apparent power. Sets the current limit — the constraint that trips first on a highly reactive load.
Watt rating
Real power. Usually the binding limit on modern IT equipment, and the figure that determines runtime.
Output power factor
Watts ÷ VA for the unit itself. Older models were 0.6; current designs are 0.9 or unity.

A 1,500 VA / 900 W unit

Given
  • Nameplate: 1,500 VA
  • Nameplate: 900 W
  • Output power factor: 0.6
Working
  1. Load at 0.9 PF: 900 W needs 1,000 VA
  2. Both limits respected

You can use the full 900 W, but never the full 1,500 VA — the watt limit stops you first on almost any real load.

Usable capacity

Live
1.5kVA rating
  • Usable real power1.4 kW
  • Apparent power1.5 kVA
The share of the rating your equipment can actually use

Common UPS and Transformer Sizes

Standard ratings with the real power each supports at your chosen power factor.

Conversion chart

Live
VAApparent power (kVA)Real power (kW)
100 VA0.10.09
250 VA0.250.225
400 VA0.40.36
500 VA0.50.45
650 VA0.650.585
750 VA0.750.675
1,000 VA10.9
1,500 VA1.51.35
2,000 VA21.8
3,000 VA32.7
5,000 VA54.5
10,000 VA109
15,000 VA1513.5
20,000 VA2018

From VA to Minutes of Runtime

Runtime depends on watts drawn and battery energy, not on the VA badge. A bigger VA number with the same battery buys you no extra minutes at all.

Minutes = (Battery Wh × efficiency) ÷ Watts × 60

Use about 0.9 for inverter efficiency, and remember lead-acid capacity falls at high discharge rates.

LoadTypical drawRuntime on a 1.5 kVA / 900 W unit
Single desktop and monitor150 W20 – 30 min
Small network rack400 W7 – 10 min
Loaded to the watt limit900 W3 – 5 min

Indicative only — always check the manufacturer runtime curve for the specific model.

Runtime is not linear

Halving the load usually more than doubles the runtime, because lead-acid batteries deliver less of their rated capacity at high discharge currents.

Real power vs VA

Live
180020,000Apparent power (VA)
1,500 VA1.35 kW
Real power available across the whole VA range at your power factor

Sizing a UPS for a Rack

  1. Add up measured watts

    Use a plug-in meter or the PDU reading, not the nameplate figures on the back of each device — nameplates are worst-case and wildly pessimistic.

  2. Add 25% headroom

    Covers growth and keeps the UPS out of the top of its range, where efficiency and runtime both suffer.

  3. Convert to VA

    Divide watts by the load power factor to get the apparent power the inverter must carry.

  4. Check both limits

    Confirm your figure sits under the unit VA rating and its watt rating.

  5. Size the runtime

    Decide whether you need ride-through for brief dips or enough time for an orderly shutdown, then pick the battery to match.

Rack UPS checklist
  • Total measured watts, plus 25%, is under the watt rating.
  • Total VA is under the VA rating.
  • Runtime covers your shutdown script with margin.
  • Outlet types and count match the equipment.
  • The heat the UPS rejects is included in the room cooling load.

Usable power by load type

Live
Legacy PSUs (0.7)
Usable
1.05 kW
Apparent
1.5 kVA
Typical IT (0.9)
Usable
1.35 kW
Apparent
1.5 kVA
Corrected (1.0)
Usable
1.5 kW
Apparent
1.5 kVA
How much of the same VA rating you can actually use

VA to kVA Questions

Common questions about converting va to kva.

Exactly 1,000 VA. Divide volt-amperes by 1,000 to reach kilovolt-amperes.

No. 1,000 VA is 1 kVA of apparent power. The real power is 1 kVA × power factor, so 0.9 kW at 0.9 PF.

The VA figure limits current through the inverter, while the watt figure limits real power the battery and electronics can sustain. Your load must respect both.

Most current models are rated at 0.9 or unity power factor. Older units were often 0.6–0.8, which made the watt rating much lower than the VA number suggested.

Divide volt-amperes by the supply voltage: amps = VA ÷ volts for single-phase, or VA ÷ (√3 × volts) for three-phase.

Not by itself. Runtime comes from battery capacity against the watts drawn. A larger VA rating with the same battery gives the same minutes.

Measured, every time. Equipment nameplates state worst-case draw and typically overstate real consumption by 30–50%.